Reference Chart for ESTIMATE only |
|
|
Table 1. Typical Fluorescent and HID Lamps (for ESTIMATE only!)
|
|
|
|
|
|
|
|
|
|
|
| Lamp Type |
Length |
Lamps |
Description |
Lamp |
Ballast |
Lumens |
System |
System |
System |
| per |
Watts |
per |
Watts** |
Watts** |
Watts** |
| Fixture |
|
Lamp* |
(BF=0.88) |
(BF=0.77) |
(BF=1.15) |
| T8 (std) |
4ft |
2 |
F32T8 |
32 |
Electronic |
2850 |
56 watts |
49 watts |
74 watts |
| T8 (prem) |
4ft |
2 |
F28T8 |
28 |
Electronic |
2550 |
49 watts |
43 watts |
65 watts |
|
| T12 (std) |
4ft |
2 |
F40T12 |
40 |
Mag-STD |
3050 |
85 watts |
|
|
| T12 (prem) |
4ft |
2 |
F34T12 |
34 |
Mag-ES |
2650 |
74 watts |
|
|
|
| T8 (std) |
4ft |
3 |
F32T8 |
32 |
Electronic |
2850 |
83 watts |
74 watts |
112 watts |
| T8 (prem) |
4ft |
3 |
F28T8 |
28 |
Electronic |
2550 |
73 watts |
65 watts |
98 watts |
|
| T12 (std) |
4ft |
3 |
F40T12 |
40 |
Mag-STD |
3050 |
130 watts |
|
|
| T12 (prem) |
4ft |
3 |
F34T12 |
34 |
Mag-ES |
2650 |
117 watts |
|
|
|
| T8 (std) |
4ft |
4 |
F32T8 |
32 |
Electronic |
2850 |
112 watts |
98 watts |
151 watts |
| T8 (prem) |
4ft |
4 |
F28T8 |
28 |
Electronic |
2550 |
98 watts |
87 watts |
132 watts |
|
| T12 (std) |
4ft |
4 |
F40T12 |
40 |
Mag-STD |
3050 |
170 watts |
|
|
| T12 (prem) |
4ft |
4 |
F34T12 |
34 |
Mag-Es |
2650 |
148 watts |
|
|
|
| T8 (std) |
8ft |
2 |
F96T8 |
59 |
Electronic |
4800 |
109 watts |
|
|
| T8 (prem) |
8ft |
4 |
F96T8 |
59 |
Electronic |
4800 |
219 watts |
|
|
|
| T12 (std) |
8ft |
2 |
F96T12 |
60 |
Mag-STD |
5500 |
138 watts |
|
|
| T12 (prem) |
8ft |
2 |
F96T12 |
60 |
Mag-ES |
5500 |
125 watts |
|
|
| T12 (std) |
8ft |
2 |
F96T12 |
75 |
Mag-STD |
6150 |
173 watts |
|
|
| T12 (prem) |
8ft |
2 |
F96T12 |
75 |
Mag-ES |
6150 |
158 watts |
|
|
|
| T12 (std) |
8ft |
2 |
F96T12/HO |
95 |
Mag-STD |
8000 |
227 watts |
|
|
| T12 (prem) |
8ft |
2 |
F96T12/HO |
95 |
Mag-ES |
8000 |
207 watts |
|
|
| T12 (std) |
8ft |
2 |
F96T12/HO |
110 |
Mag-STD |
8900 |
257 watts |
|
|
| T12 (prem) |
8ft |
2 |
F96T12/HO |
110 |
Mag-ES |
8900 |
237 watts |
|
|
| T12 (std) |
8ft |
2 |
F96T12/VHO |
185 |
Mag-STD |
12500 |
380 watts |
|
|
| T12 (prem) |
8ft |
2 |
F96T12/VHO |
185 |
Mag-ES |
12500 |
326 watts |
|
|
| T12 (std) |
8ft |
2 |
F96T12/VHO |
215 |
Mag-STD |
13500 |
440 watts |
|
|
| T12 (prem) |
8ft |
2 |
F96T12/VHO |
215 |
Mag-ES |
13500 |
378 watts |
|
|
|
| T5 HO |
46" |
2 |
F54T5 |
54 |
Electronic |
5,000 |
120 watts, BF = 1.0 |
|
| T5 HO |
46" |
4 |
F54T5 |
54 |
Electronic |
5,000 |
240 watts, BF = 1.0 |
|
| T5 HO |
46" |
6 |
F54T5 |
54 |
Electronic |
5,000 |
360 watts, BF = 1.0 |
|
|
| Metal Halide |
1 |
MH100 |
100 |
CWA |
6,500 |
128 watts, BF = 1.0 |
|
| Metal Halide |
1 |
MH250 |
250 |
CWA |
13,500 |
295 watts, BF = 1.0 |
|
| Metal Halide |
1 |
MH100 |
400 |
CWA |
24,000 |
458 watts, BF = 1.0 |
|
| Ceramic Metal Halide |
1 |
CMH250 |
250 |
Electronic |
22,000 |
285 watts, BF = 1.0 |
|
| Ceramic Metal Halide |
1 |
CMH400 |
400 |
Electronic |
38,000 |
435 watts, BF = 1.0 |
|
| High Pressure Sodium |
1 |
HPS100 |
100 |
CWA |
9,500 |
138 watts, BF = 1.0 |
|
| High Pressure Sodium |
1 |
HPS250 |
250 |
CWA |
25,600 |
295 watts, BF = 1.0 |
|
| High Pressure Sodium |
1 |
HPS400 |
400 |
CWA |
50,000 |
450 watts, BF = 1.0 |
|
| Mercury Vapor |
1 |
MV100 |
100 |
CWA |
4,300 |
125 watts, BF = 1.0 |
|
| Mercury Vapor |
1 |
MV250 |
250 |
CWA |
10,500 |
290 watts, BF = 1.0 |
|
| Mercury Vapor |
1 |
MV400 |
400 |
CWA |
16,500 |
455 watts, BF = 1.0 |
|
|
| Incandescent |
1 |
60 watts |
60 |
n/a |
1,000 |
60 watts |
|
|
| Incandescent |
1 |
100 watts |
100 |
n/a |
1,700 |
100 watts |
|
|
| Incandescent |
1 |
200 watts |
200 |
n/a |
2,500 |
200 watts |
|
|
|
|
|
|
|
|
|
|
|
|
| * Lumens must be multiplied by ballast factor (BF) to get estimated lumen output per lamp. Also, lumen |
| depreciation is generally in the range of 5 to 30%, and should be considered in the actual lighting design. |
| ** This is a rough estimate only. There is a tremendous range of performance based on manufacturer, age |
| of lamp, lumen output, type of ballast, ballast factor, CRI, etc. Actual figures should be obtained directly |
| from manufacturer for a proper calculation. Note that fixture watts change as ballast factor (BF) changes. |
|